原産地: | 中国(本土) | 銘柄: | 勝利 | モデル番号: | Fc-01 | タイプ: | スプライス | モデル: | Fc-01 | 材料: | ステンレス鋼 | 形状: | 円筒形端子 | 端子直径: | 35mm | 端末高さ: | 45ミリメートル | 全体の高さ: | 240ミリメートル | 鋼棒直径: | 16mm | めねじ直径: | 16mm | 重量: | 590ミリメートル |
包装
包装: | カートン又は合板 |
仕様
stainless steel discharge terminal FC-01
Introduction:
FC stainless steel earthing terminal are metal casting or mechanical parts for grounded system or. Made by selected 99.99% high conductive copper cathode or 316 stainless steel.
Application:
Mainly used in high-speed rail,electrified railway,bridge and tunnel,pier etc.
Technial data:
Items | Model | Terminal diameter | Terminal height | Total height | Steel rod diameter | Female thread diameter | Weight |
stainless steel | FC-01 | 35 | 45 | 240 | 16 | 16 | 590 |
stainless steel | FC-02 | 35 | 45 | 180 | 16 | 16 | 590 |
stainless steel | FC-03 | 35 | 45 | 220 | 16 | 16 | 590 |
Why choose us?
Big Ability
*We supply various standard size non-ferrous metal castings,in high quality and lower price than similar suppliers.
*Can provide all kinds of standard size non-ferrous metal pouring castings according to customers ‘ requirements.
Many Experiences
*Our products had been heavy used in the passenger dedicated line in China.
Quality gurantee:
*Detected by Product quality supervision and inspection center on a regular basis.
Inspection
- The ministry of railways product quality supervision and inspection center for communication signal inspection report
No.
Inspection item
Technical requirements
unit
Inspection result
1
C
≤0.08
%
0.02
2
Cr
≥16
%
17.00
3
Ni
≥5
%
12.31
4
Mo
≥2
%
2.09
5
Connect area between terminal and rebar
≥200
mm²
516.7
Wuhan high voltage research institute test inspection report
No.
Inspection item
Standard requirements
Inspection result
evaluate
1
DCR
<0.5×106µΩ
Before test: Short-term tolerance current
Environment temperature:25.5°C
DCR:335µΩ
Meet the requirements
After test: Short-term tolerance current
Environment temperature:24.5°C
DCR:301µΩ
Meet the requirements
2
Short-term tolerance current testing
Short-term current:40kA
Through-flow time:≥0.1s The welds not fusing
After test of 40.2 kA/0.2s,the sample welds not fusing
Meet the requirements
3
Tensile strength testing
≥167MPa
Tensile strength:93.5kN
Section :200mm²
467.5MPa
Meet the requirements
picture: